Country

Language

Currency


EYC TP02 Temperature Transmitter for DIN-Rail Type

EYC TP02 Temperature Transmitter for DIN-Rail Type

Last Update

Price:

R.F.Q.

Features -Special IC for RTD; high accuracy is assured. -TP02 with smaller volume so lesser space for installation is required. -High quality and low price. -DIN-rail type; quick to install

Share Product:

Detail

Applications

-Monitoring for long-distance temperature signal transmission.•

-For industries in heating / ventilation / air conditioning / cooling /water power / electricity, etc.

-For process in agriculture / green house / environmental engineering /food / pharmaceutical industry.


INPUT Input…….................................................................PT 100Ω (3-wire)

Cable resistance …….......≤ 50 Ω (3 wires with the same resistance)

PT100Ω sensor current …….................................................< 0.8mA

ZERO adjustment range ……...................................................±10 %

SPAN adjustment range ……...................................................±10 %


OUTPUT

Output ……...............................................................4~20mA ; 2-wire

Accuracy ……..............................................................± 0.1 % of F.S.

Load resistance …….....................≤ (supply voltage - 8 V) / 0.02A Ω

Load resistance stability …….....................................±0.05% / 100Ω

Power stability ……........................................................±0.025% / V

Temperature drift ……............................................< ±0.015% fs / °C

Calibration temperature ……................................................20~28°C

Response time…….............................................................< 250 ms


PROTECTION

PT100Ω signal disconnection protection & output ……..........> 23mA

PT100Ω signal short circuit protection & output ……...............< 3mA

Output polarity protection …….....................................................Yes


ELECTRICAL SPECIFICATION

Power supply ……....................................10~30 VDC / 90~260 VAC

Operation frequency ……................................................AC47-63Hz

Working environment …….............-20~60°C ; 0~95% rh (non-cond.)

Protection degree ……..........................housing IP30 ; terminal IP10

Housing ……...............................................................................ABS

Catalogue Download

Find Nearby Companies
Zoom in to view more information