EYC TP04/ TD04 2-Wire / Digital Temperature Transmitter for Duct Type
Last Update
Price:
R.F.Q.
Share Product:
Detail
Applications
-Monitoring for long-distance temperature signal transmission.
-Signal transfer from PT sensor to 4-20mA.
-For industries in heating / ventilation / air conditioning / cooling / water power/ electricity, etc.
-For process in agriculture / green house / environmental engineering /food / pharmaceutical industry.
-Machinery manufacturing / storage tank / compressor / hydraulic equipment.
PT100Ω sensor current …….................................................< 0.8mA
ZERO adjustment range ……...................................................±10 %
SPAN adjustment range ……............................................................. .........................................TP04: ±10%/ TD04: computer calibration
OUTPUT
Output …….............................................................. 4~20mA ; 2-wire
Accuracy ……...............................................................±0.5 % of F.S.
Load resistance …….....................≤ (supply voltage - 8 V) / 0.02A Ω
Power stability ……........................................................± 0.025%/V
Temperature drift ……............................................< ±0.015% fs / °C
Calibration temperature ……................................................20~28°C
Response time…….............................................................< 250 ms
PROTECTION
PT100Ω signal disconnection protection & output ……...................... ........................................................TP04: > 23mA;TD04: > 22mA
PT100Ω signal short circuit protection & output ……......................... .........................................................TP04: < 3mA;TD04: < 3.6mA
Output polarity protection …….....................................................Yes
ELECTRICAL REGULATION
Power supply ……...........................................................10~30 VDC
Working environment ……..............-20~80°C;100% rh (non-cond.)
Storage temperature……....................................................-40~85°C
Electrical connector …….................................................................... .................................TP04: DIN 43650 ABS / TD04: M12 connector
Protection degree …….............................TP04: IP 65;TD04: IP 67
Housing …….........................................................................SUS304
Weight ……..................................50mm - TP04: 250g / TD04: 180g …................................................200mm - TP04: 260g / TD04: 200g
Option ……...............30mm / 80mm / 130mm / 180mm R1/2" sleeve
Specification